EPA 608 Type III Practice Test: Real Questions & Answers (Low-Pressure Chillers)
Type III covers low-pressure appliances — primarily large centrifugal chillers using R-11, R-123, R-245fa, or R-1233zd(E). The most distinctive Type III topics are sub-atmospheric operation (the low side runs in vacuum, so leaks pull air IN rather than refrigerant out), purge units (unique to Type III), rupture discs (15 psig safety relief), and R-123 toxicity (B1 safety class requires respiratory protection in confined rooms). All 30 questions below are grounded in EPA primary sources with 40 CFR citations where applicable.
- • Type III is 25 multiple-choice questions (closed-book only)
- • You must also pass the Core section to earn Type III certification
- • Type III is closed-book only — no reference materials permitted during the exam
- • Passing threshold: 72% (18 of 25 correct)
- • Section 608 certifications do not expire — once you pass, you're permanently certified
- • Type III has the deepest evacuation requirement of any appliance class — 25 mm Hg absolute
Type III — Low-Pressure Appliances (30 questions)
For technicians working on low-pressure appliances — primarily large centrifugal chillers using R-11, R-123, R-245fa, or R-1233zd. Most distinctive Type III topics: sub-atmospheric operation (low side runs in vacuum, so leaks pull air IN rather than refrigerant OUT), purge units (unique to Type III), rupture discs (15 psig safety relief), and R-123 toxicity handling (B1 safety class). The 25 mm Hg absolute evacuation requirement is the deepest of any Section 608 appliance class. Closed-book only.
- A.Any refrigerant operating below 50 psig discharge pressure
- B.Refrigerants with boiling point ABOVE 50°F at atmospheric pressure
- C.Any refrigerant that requires sub-atmospheric operation
- D.Only refrigerants used in absorption chillers
Show answer & explanation
Correct answer: B. Refrigerants with boiling point ABOVE 50°F at atmospheric pressure
Low-pressure refrigerants have boiling points above 50°F at atmospheric pressure (R-11, R-123, R-245fa, R-1233zd). At normal temperatures, they are partially vapor; the system must operate in vacuum to condense them.
- A.Residential central AC
- B.Rooftop packaged unit
- C.Centrifugal chillers using R-123
- D.Walk-in freezers
Show answer & explanation
Correct answer: C. Centrifugal chillers using R-123
Type III covers low-pressure appliances — primarily large centrifugal chillers (water-cooled) using R-11, R-123, R-245fa, or R-1233zd. Residential AC, RTUs, and walk-ins are Type II (high-pressure).
- A.Because chillers use absorption rather than mechanical compression
- B.Because low-pressure refrigerants have boiling points ABOVE 50°F at atmospheric pressure, so the saturation pressure at typical evaporator temperatures (~40°F) is below atmospheric
- C.Because the purge unit removes positive pressure from the system
- D.Because centrifugal compressors cannot maintain positive suction pressures
Show answer & explanation
Correct answer: B. Because low-pressure refrigerants have boiling points ABOVE 50°F at atmospheric pressure, so the saturation pressure at typical evaporator temperatures (~40°F) is below atmospheric
Boiling point above 50°F at 1 atm means saturation pressure at typical chiller evaporator temps (~40°F) is below 1 atm — sub-atmospheric. Creates the air-infiltration / non-condensable accumulation challenge unique to Type III.
- A.10 inches Hg vacuum
- B.15 inches Hg vacuum
- C.25 mm Hg absolute
- D.0 inches Hg (atmospheric)
Show answer & explanation
Correct answer: C. 25 mm Hg absolute
Per 40 CFR 82.156: low-pressure appliances require evacuation to 25 mm Hg absolute (≈29 in Hg vacuum) with post-1993 equipment — the deepest evacuation of any appliance class. Critical Type III question.
Reference: 40 CFR 82.156, Appendix B
- A.25 mm Hg absolute
- B.29 inches Hg vacuum
- C.25 mm Hg vacuum (gauge)
- D.5 psig
Show answer & explanation
Correct answer: A. 25 mm Hg absolute
Pre-1993 equipment on low-pressure appliances must achieve 25 mm Hg absolute — SAME as post-1993. Type III is the only category where pre/post-1993 evacuation requirements are identical. The 5 psig exception applies only during oil change with the compressor running.
Reference: 40 CFR 82.156, Appendix B
- A.Below atmospheric (vacuum only)
- B.0 psig (atmospheric)
- C.5 psig
- D.10 psig
Show answer & explanation
Correct answer: C. 5 psig
82.156 provides an exception during oil changes performed with the compressor running: the appliance may be pressurized up to 5 psig. Normal recovery requires 25 mm Hg absolute, but this isn't practical during running oil changes.
Reference: 40 CFR 82.156
- A.Add refrigerant during operation
- B.Remove non-condensable gases (primarily air and water vapor) that infiltrate the sub-atmospheric system
- C.Pressurize the system for leak testing
- D.Cool the compressor motor
Show answer & explanation
Correct answer: B. Remove non-condensable gases (primarily air and water vapor) that infiltrate the sub-atmospheric system
Purge units remove non-condensable gases (air, water vapor) that infiltrate through leaks in sub-atmospheric systems. Non-condensables raise discharge pressure, reduce capacity, and waste energy. Purge units are UNIQUE to low-pressure systems.
- A.Bottom of the evaporator
- B.Top of the condenser
- C.Compressor discharge line
- D.Receiver
Show answer & explanation
Correct answer: B. Top of the condenser
Non-condensables accumulate at the top of the condenser (lower density than refrigerant vapor). Purge units draw from there to capture and remove them.
- A.Compressor wear
- B.Refrigerant loss while removing non-condensables
- C.Oil consumption
- D.Water-side fouling
Show answer & explanation
Correct answer: B. Refrigerant loss while removing non-condensables
High-efficiency purge units separate refrigerant vapor from non-condensables, returning the refrigerant to the system and venting only the non-condensables. Older purges vented both, causing significant refrigerant loss.
- A.Refrigerant overcharge
- B.The chiller likely has a leak allowing air to infiltrate the sub-atmospheric portion of the system
- C.Normal operation — purges always run continuously
- D.Compressor wear
Show answer & explanation
Correct answer: B. The chiller likely has a leak allowing air to infiltrate the sub-atmospheric portion of the system
Excessive purge cycling indicates air infiltration, which means there's a LEAK on the sub-atmospheric (low) side. Counter-intuitive: leaks in low-pressure systems pull AIR IN (not refrigerant out). Excessive purging = leak indicator.
- A.Low-pressure refrigerants don't react with leak detectors
- B.The system operates in vacuum on the low side, so air leaks IN rather than refrigerant leaking OUT — standard sniff tests at atmospheric conditions won't find them
- C.Low-pressure systems have fewer joints to inspect
- D.Type III refrigerants are colorless and odorless
Show answer & explanation
Correct answer: B. The system operates in vacuum on the low side, so air leaks IN rather than refrigerant leaking OUT — standard sniff tests at atmospheric conditions won't find them
Low-pressure systems pull air IN through leaks (not refrigerant out). Standard electronic detectors that sniff for refrigerant won't find a leak unless the system is pressurized above atmospheric. Type III leak detection often requires pressurizing the system.
- A.5 psig
- B.10 psig (limited by the rupture disc setting)
- C.50 psig
- D.150 psig
Show answer & explanation
Correct answer: B. 10 psig (limited by the rupture disc setting)
Pressurizing for leak testing must stay below the rupture disc pressure (typically 15 psig). Standard practice limits test pressure to 10 psig with dry nitrogen — only slight pressurization is needed to bring the system above atmospheric so leaks become detectable.
- A.Releases excess refrigerant during normal operation
- B.Provides emergency pressure relief if system pressure rises above design limits — protects equipment designed for sub-atmospheric operation
- C.Allows refrigerant addition during service
- D.Vents the purge unit
Show answer & explanation
Correct answer: B. Provides emergency pressure relief if system pressure rises above design limits — protects equipment designed for sub-atmospheric operation
Rupture discs are emergency pressure-relief devices. Low-pressure chillers are designed for sub-atmospheric operation — high pressure (e.g., from fire) could rupture the vessel. The disc breaks at ~15 psig to relieve pressure before catastrophic failure.
- A.5 psig
- B.15 psig
- C.30 psig
- D.50 psig
Show answer & explanation
Correct answer: B. 15 psig
Rupture discs on low-pressure systems are typically set at 15 psig per ASHRAE standards. Pressurizing beyond this could rupture the disc and release the entire refrigerant charge.
- A.Reset the disc with a manual lever
- B.Replace the rupture disc — they are one-time-use devices
- C.Pressurize the system to reseat the disc
- D.Drain the condenser and refill
Show answer & explanation
Correct answer: B. Replace the rupture disc — they are one-time-use devices
Rupture discs are ONE-TIME-USE — they physically rupture (break open) to relieve pressure. Once activated, the disc must be physically replaced. The chiller must also be inspected for the cause of the over-pressure event.
- A.These refrigerants are inherently unstable
- B.Their boiling points at atmospheric pressure are above typical room temperatures (R-123 BP ≈ 82°F), so at normal room temp and 1 atm they exist as liquid that wants to vaporize
- C.Atmospheric pressure compresses them
- D.Catalysts in copper tubing trigger phase change
Show answer & explanation
Correct answer: B. Their boiling points at atmospheric pressure are above typical room temperatures (R-123 BP ≈ 82°F), so at normal room temp and 1 atm they exist as liquid that wants to vaporize
R-123's BP at 1 atm is ~82°F. At room temp (68–77°F) and atmospheric pressure, R-123 is at saturation conditions — readily vaporizes. Why low-pressure chillers must run in vacuum to maintain liquid refrigerant at typical chiller temperatures.
- A.Low-pressure refrigerants are more viscous
- B.The system must be pulled to a much deeper vacuum (25 mm Hg absolute), and the low operating pressure creates a small pressure differential into the recovery vessel
- C.Type III certification requires extra paperwork between steps
- D.Low-pressure systems contain less refrigerant
Show answer & explanation
Correct answer: B. The system must be pulled to a much deeper vacuum (25 mm Hg absolute), and the low operating pressure creates a small pressure differential into the recovery vessel
Recovery requires pulling to 25 mm Hg absolute — much deeper than high-pressure. Small pressure differential between sub-atmospheric refrigerant and recovery vessel makes the process slow. Heating the chiller barrel (warm water circulation) is often required.
- A.Keeps the refrigerant in vapor form for faster recovery
- B.Prevents ice formation that could damage tubes; maintains adequate refrigerant pressure for transfer; speeds recovery
- C.Cleans the heat exchanger before service
- D.Reduces purge unit operation
Show answer & explanation
Correct answer: B. Prevents ice formation that could damage tubes; maintains adequate refrigerant pressure for transfer; speeds recovery
During recovery, the chiller barrel cools dramatically. Without warm water circulation, residual moisture can freeze and damage tubes. Warm water also keeps refrigerant pressure high enough for efficient transfer.
- A.The compressor will short-cycle
- B.Ice can form in the tube bundle and freeze/damage the tubes — saturation temperature of residual water drops to freezing under deep vacuum
- C.The purge unit will fail
- D.Refrigerant will leak through the rupture disc
Show answer & explanation
Correct answer: B. Ice can form in the tube bundle and freeze/damage the tubes — saturation temperature of residual water drops to freezing under deep vacuum
Deep vacuum drops the saturation temperature of any residual water to freezing. Ice formation expands and can damage tubes. Preventive: keep warm water circulating to maintain tube-metal temperatures above 32°F.
- A.-41°F (same as R-22)
- B.32°F
- C.82°F (just above room temperature)
- D.118°F
Show answer & explanation
Correct answer: C. 82°F (just above room temperature)
R-123 BP ≈ 82°F at 1 atm. At typical room temp (68–77°F), R-123 vapor pressure is just below atmospheric — must operate in slight vacuum to condense. PT chart for R-123 shows vacuum at typical chiller temps.
- A.A1 — non-toxic, non-flammable; no special equipment
- B.B1 — higher toxicity, lower flammability; equipment rooms require refrigerant detectors and alarms, technicians use respiratory protection when concentrations may be elevated
- C.A2L — mildly flammable; explosion-proof electrical required
- D.B2L — toxic and mildly flammable
Show answer & explanation
Correct answer: B. B1 — higher toxicity, lower flammability; equipment rooms require refrigerant detectors and alarms, technicians use respiratory protection when concentrations may be elevated
R-123 is B1: 'B' = higher toxicity (effects below 400 ppm); '1' = no significant flammability. Triggers ASHRAE 15 requirements for machinery rooms: detectors with alarms, ventilation, emergency shutdown. Differs from newer R-1233zd (A1).
- A.B1 — same as R-123
- B.A2L — mildly flammable
- C.A1 — non-toxic and non-flammable; a significant safety improvement over R-123's B1
- D.B2 — more toxic than R-123
Show answer & explanation
Correct answer: C. A1 — non-toxic and non-flammable; a significant safety improvement over R-123's B1
R-1233zd(E) is A1 — safest classification, neither significant toxicity nor flammability. Major safety improvement over R-123 (B1). Still operates sub-atmospheric like R-123, so Type III certification and techniques apply.
- A.CO2 fire suppression rated for refrigerant fires
- B.Electronic refrigerant detectors and audible/visual alarms that activate when concentrations exceed safe thresholds
- C.Class 1 Division 2 explosion-proof electrical throughout
- D.Positive-pressure air supply to dilute any release
Show answer & explanation
Correct answer: B. Electronic refrigerant detectors and audible/visual alarms that activate when concentrations exceed safe thresholds
ASHRAE Standard 15 requires electronic refrigerant detectors with alarms in machinery rooms housing refrigeration equipment — including B1 refrigerants like R-123. Must trigger at or below the ASHRAE 34 toxicity limit.
- A.No special measures needed
- B.Wear flame-resistant clothing only
- C.Ventilate the area, avoid direct skin and eye contact with liquid, use appropriate respiratory protection when concentrations may be elevated
- D.Ventilate only when detector alarm sounds
Show answer & explanation
Correct answer: C. Ventilate the area, avoid direct skin and eye contact with liquid, use appropriate respiratory protection when concentrations may be elevated
R-123 is B1 (higher toxicity). Safe handling: ventilate area; avoid direct contact with liquid (causes irritation, frostbite); use respiratory protection when vapor concentrations may be elevated. Not flammable (class 1) — toxicity is the primary concern.
- A.Oxygen reacts with refrigerant to form acids
- B.Compressed air raises pressure too quickly
- C.Oxygen can combine with compressor oil under pressure to create an explosive mixture — fire and explosion hazard
- D.Compressed air contains too much moisture
Show answer & explanation
Correct answer: C. Oxygen can combine with compressor oil under pressure to create an explosive mixture — fire and explosion hazard
Oxygen mixed with hydrocarbon-based compressor oil under elevated pressure creates conditions for a violent exothermic reaction — effectively a diesel-cycle explosion inside the refrigerant circuit. Use only DRY NITROGEN for leak testing. On low-pressure systems, limit to 10 psig to protect the rupture disc.
- A.Thermal expansion valve
- B.Filter-drier
- C.Purge unit
- D.Suction-line accumulator
Show answer & explanation
Correct answer: C. Purge unit
Purge unit is unique to low-pressure appliances. Its function (continuously removing non-condensables from sub-atmospheric systems) has no analog in high-pressure systems, which maintain positive pressure and expel refrigerant outward through leaks.
- A.35% of full charge
- B.15% of full charge
- C.10% of full charge
- D.5% of full charge
Show answer & explanation
Correct answer: C. 10% of full charge
Current 40 CFR 82.157 sets comfort cooling threshold at 10% per 12-month period. Centrifugal R-123 / R-11 chillers used for HVAC comfort cooling fall in this category. Older materials may cite 15% (pre-2019); current is 10%.
Reference: 40 CFR 82.157
- A.Repair within 7 days; no extensions
- B.Either repair the leak within 30 days of discovery OR develop a written retrofit/retirement plan within 30 days
- C.EPA notification within 14 days; repair at next scheduled maintenance
- D.Repair within 90 days; log entry only
Show answer & explanation
Correct answer: B. Either repair the leak within 30 days of discovery OR develop a written retrofit/retirement plan within 30 days
30-day decision point: either repair within 30 days OR develop a written retrofit/retirement plan within 30 days. If retrofit/retirement: planned action must generally be completed within 1 year. Follow-up verification testing also required.
Reference: 40 CFR 82.157
- A.R-22 and R-410A
- B.R-134a and R-404A
- C.R-11, R-123, R-245fa, and R-1233zd(E)
- D.R-32 and R-454B
Show answer & explanation
Correct answer: C. R-11, R-123, R-245fa, and R-1233zd(E)
Low-pressure chillers historically used R-11 (CFC, phased out). R-123 (HCFC) became the standard replacement. R-245fa (HFC) and R-1233zd(E) (HFO) are newer alternatives. R-22, R-410A, R-134a are high-pressure (Type II).
- A.Uses a piston to compress refrigerant
- B.Uses high-speed rotating impeller(s) to dynamically compress refrigerant — well-suited to low-pressure refrigerants and large cooling capacities
- C.Uses an absorption process instead of mechanical compression
- D.Requires a special evaporator design
Show answer & explanation
Correct answer: B. Uses high-speed rotating impeller(s) to dynamically compress refrigerant — well-suited to low-pressure refrigerants and large cooling capacities
Centrifugal compressors use high-speed rotating impellers to dynamically compress refrigerant. Well-suited to low-pressure refrigerants (R-123, R-1233zd) and large cooling capacities (200–10,000+ tons). The most common large-tonnage chiller technology.
- Core Section Practice Test — Universal regulatory knowledge required for all certification types
- Type I Practice Test — Small appliances (factory-sealed, ≤5 lbs of refrigerant)
- Type II Practice Test — High and very high-pressure appliances (the most commonly held credential)
- Back to Full Study Guide Hub — All 127 Q&A across Core, Type I, Type II, and Type III in one page
Get EPA 608 Universal Certified — Free with RefriTrak
RefriTrak annual plan subscribers get 4 free EPA 608 Universal certifications per year (one per quarter, $30 value each) through our partnership with SkillCat. Study with this guide, then certify your team.